The ZERO-Hertz trip unit is a solid state overcurrent device for use on one and two pole DC circuit breakers in voltage classes up to 1,000 volts. The ZERO-Hertz® comes standard with long-time, short-time, instantaneous, ground fault, and reverse current. All of the protective features except long time can be turned off to allow for greater coordination and flexibility of use.
Done using the buttons and 16 character backlight LCD display on the front of the unit. An integrated security key prevents accidental modification of settings.
All settings are made in amps and seconds. The LCD displays the current during normal operation and shows the phase currents and type of trip after an event.
The number, type of trip events and commissioning data are accessible from the front panel. This data can also be cleared or modified at anytime from the front panel.
The ZERO-Hertz also has a “SELF TEST OK” led that verifies the unit is functioning properly. There is also a “PICK-UP” LED that indicates when the current reaches or exceeds the long-time pick up value.
All CTs are specifically designed for use with the AC-PRO family of trip units.
Utility Relay Company manufacturers split core CTs for use as neutral CTs in 4 wire systems. The split cores make it very easy to install the CT on existing bus or cable. Each split core has phenolic plates with punch outs to match standard sizes/shapes of cable or bus-work.